82
Manual – Fieldbus Interface DFE24B EtherCA
9
Diagnostic procedures
Error Diagnostics
9 Error Diagnostics
9.1 Diagnostic procedures
The diagnostics procedures described in the following section demonstrate the fault
analysis methods for the following problems:
Inverter does not operate on EtherCAT
®
Inverter cannot be controlled using the EtherCAT
®
master.
For more information dealing specifically with the inverter parameter settings for various
fieldbus applications, refer to the "MOVIDRIVE
®
MDX60B/61B Communication and
Fieldbus Unit Profile" manual and the MOVIDRIVE
®
MDX60B/61B system manual.
Step 1: Check the connection between the inverter and EtherCAT
®
Step 2: Response of the RUN LED?
Is the bus connected plugged into the master/inverter? NO [A]
YES
How is the Link/activity LED reacting on option DFE24B? OFF
[A]
ON
Is the physical connection between the inverter and EtherCAT
®
OK?
Make sure EtherCAT
®
is connected correctly at X30 IN (incoming
EtherCAT
®
connection) / X31 OUT (outgoing EtherCAT
®
connection).
NO
[A]
YES
Continue with 2: Response of the RUN LED?
[A] Check the bus cabling.
OFF Has the master switched the slave to INIT state?
YES
NO
[A]
[B]
Flashing green Slave is in PRE-OPERATIONAL state.
[C]
Lights up green
once
Slave is in SAFE-OPERATIONAL state.
[C]
Lights up green Slave is in OPERATIONAL state.
[C]
[A] Startup the bus in the master.
[B] Option DFE24B is defective.
[C] Continue with 3: Response of the ERR LED?