Service
Fault/error table
Operating Instructions – MOVIMOT
®
flexible
218
Subfault: 16.8
Description: Temperature sensor motor 1
Response: Output stage inhibit
Cause Measure
Faulty startup of temperature sensor of motor1. Perform startup again.
Subfault: 16.9
Description: Temperature sensor motor 2
Response: Output stage inhibit
Cause Measure
Faulty startup of temperature sensor of motor2. Perform startup again.
Subfault: 16.10
Description: Actual position source not assigned
Response: Application stop + output stage inhibit
Cause Measure
Active control mode requires an encoder for posi-
tion mode.
– Assign actual position source in encoder as-
signment of the active drive train (Index 8565.3 or
8566.3).
– If no encoder is installed, activate the FCBs
only using "torque control" or "speed control" op-
erating mode.
Subfault: 16.11
Description: Motor data calculation error
Response: Output stage inhibit
Cause Measure
Motor startup not possible because of inconsist-
ent motor data or wrong device configuration
data.
Check the motor data for plausibility, or contact
SEW‑EURODRIVE Service.
Subfault: 16.12
Description: Motor data write sequence
Response: Output stage inhibit
Cause Measure
Subindex 1 not written to zero before writing elec-
trical startup parameters (index 8357, 8360,
8394, 8420 or 8358, 8361, 8395, 8421).
Reset the fault. Set parameters 8360/1 or 8361/1
to "0" before writing additional parameters.