Fault/error table
Operating Instructions – MOVIMOT
®
flexible
219
Subfault: 16.20
Description: Nominal speed too high or nominal frequency too low
Response: Output stage inhibit
Cause Measure
During startup using nameplate data: Nominal
speed too high or nominal frequency too low. The
resulting number of pole pairs is 0.
Enter plausible motor data (nominal speed and
nominal frequency).
Subfault: 16.21
Description: Nominal slip negative
Response: Output stage inhibit
Cause Measure
During startup using nameplate data, the calcu-
lated nominal slip is negative: Nominal frequency
too low, or nominal speed too high, or number of
pole pairs too high.
Enter plausible motor data (nominal frequency,
nominal speed, number of pole pairs).
Subfault: 16.22
Description: Specify the number of pole pairs
Response: Output stage inhibit
Cause Measure
During startup using nameplate data: It is not
possible to calculate the number of pole pairs ac-
curately from nominal frequency and nominal
speed.
Enter the number of pole pairs.
Subfault: 16.23
Description: Plausibility check failed
Response: Output stage inhibit
Cause Measure
During startup using nameplate data: The estim-
ated nominal power does not match the entered
nominal power.
Check entered nameplate data for plausibility.
Subfault: 16.24
Description: Speed controller sampling cycle not possible with current PWM frequency or current
control mode
Response: Application stop + output stage inhibit
Cause Measure
At a PWM frequency of "2.5kHz", only the speed
controller sampling cycle of 2ms is permitted. For
the ELSM
®
control mode, the only permitted
speed controller sampling cycles are 1ms and
2ms.
Increase PWM frequency or increase sampling
cycle of speed controller to 2ms. Set the
sampling cycle to 1ms or 2ms for ELSM
®
control
mode.