Outputs OSSD1 and OSSD2 carry voltage, the UE10-3OS is switched on. When
t
he protective field is interrupted, the OSSD1 and OSSD2 outputs switch the
UE10-3OS off.
F
ault analysis
Cross-circuits and short-circuits of the OSSDs are recognized and lead to the lock‐
in
g state (lock-out). The malfunction of the UE10-3OS is detected. The shut-down
function is retained. Manipulation (e.g., jamming) of the S1 pushbutton prevents
the output circuits from being enabled.
T-connector UE48-2OS safety relay, with restart interlock and external device monitoring (EDM)
deTec4
0 V
§ PELV
+24 V
Com1
OSSD1
OSSD2
0 V
+24 V
5
3
4
2
1
UE48-2OS2D2
S34 S21S35 S22
S33 S12S11 S31
14A2 24 32
13A1 23 31
k2
k1
K1 K2
k2
z
k1 k2
k1
z
x y
x
!
"
y
0 V
Com1
In1
+24 V
In2
5
3
2
1
4
S1
5
3
4
2
1
5
3
4
2
1
5
3
4
2
1
E132906/00/2015-04-07
r
s
Figure 33: Connection diagram: 5-pin, T-connector, UE48-2OS, with restart interlock and external device monitoring (EDM)
1) Output circuits. These contacts must be incorporated into the control such that the
d
angerous state is brought to an end if the output circuit is open. For categories 4 and
3, they must be incorporated on two channels (x, y paths). Single-channel incorporation
into the control (z path) is only possible with a single-channel control and taking the risk
analysis into account.
2) External device monitoring is only static.
3) SELV/PELV safety extra-low voltage.
T
ask
Connection of a deTec4 Ex II 3GD safety light curtain to a UE48-2OS safety relay.
Oper
ating mode: with restart interlock and external device monitoring (EDM). The
T-connector establishes a connection between the sender and the receiver.
Mode of oper
ation
When the protective field is clear, the OSSD1 and OSSD2 outputs carry voltage.
T
he system can be switched on when K1 and K2 are in a fault-free de-energized
position. The UE48-2OS is switched on by pressing S1 (pushbutton is pressed
and released). The outputs (contacts 13-14 and 23-24) switch the K1 and K2
contactors on. When the protective field is interrupted, the OSSD1 and OSSD2
outputs switch the UE48-2OS off. Contactors K1 and K2 are switched off.
4 P