Figure 55: DIP switches for scanning ranges on SP2 system plug
Table 30: DIP switches and scanning range
DIP switch 1 (row B) DIP switch 2 (row B) Function
Off Off Automatic calibration of the
pr
otective field width (delivery
condition)
Off On Dynamic protective field width
(small range)
On Off Dynamic protective field width
(medium range)
On On Dynamic protective field width
(
large range)
Note on configuration
b
Chec
k the parity after setting the DIP switch, see "Checking the parity", page 94.
7.7 Configuring reduced resolution
Important information
NOTE
R
educed resolution is only configured on the receiver of a single or host system.
Prerequisites
•
SP2 s
ystem plug
Configuring reduced resolution
R
educed resolution is configured using DIP switches 3 and 4 (row B) on the system plug
of the receiver.
The reduced resolution configuration is taken on by all guest devices in a cascade.
7 C
ONFIGURATION
92
O P E R A T I N G I N S T R U C T I O N S | deTec4 Ex II 3GD 8023872/18YZ/2021-01-14 | SICK