Configuring muting
OFF
uncoded
code 1
code 2
rev.conf.
ON
1 2 3 4
O F F
1 2 3 4
O F F
1 2 3 4
O F F
1
O N
2
A
B
C
D
1 2 3 4
O F F
Figure 54: DIP switch for muting on the SP2 system plug
T
able 29: DIP switch and muting
DIP switch 1
(r
ow A)
DIP switch 2
(row A)
DIP switch 3
(row A)
DIP switch 4
(row A)
Function
Off Off Off Off Muting deactivated
(delivery condition)
Off On Off Off Cross muting
Off On Off On Cross-muting with muting
si
gnal 1 on system con‐
nection In4 and muting
signal 2 on extension
connection In2
Off On On Off Partial blanking based on
cross-muting
Off On On On Partial blanking based on
cr
oss-muting with muting
signal 1 on system con‐
nection In4 and muting
signal 2 on extension
connection In2
On Off Off Off Exit monitoring
1)
2)
3)
On Off Off On Exit monitoring with mut‐
ing signal 1 on system
connection In4 and mut‐
ing signal 2 on extension
connection In2
1)
2)
3)
On Off On Off Partial blanking based on
exit monitoring
1)
2)
3)
7 CONFIGURATION
90
O P E R A T I N G I N S T R U C T I O N S | deTec4 Ex II 3GD 8023872/18YZ/2021-01-14 | SICK
Subject to change without notice