Name Description
[MF2 Service] Level
Warning
The output switches when the signal attenuation value reaches the criti‐
cal value, for example due to contamination.
Options
off
on
Factory setting
on
[MF2 Service] Temp.
Warning
The output switches when the interior device temperature reaches the
critical value.
Options
off
on
Factory setting
on
[MF2 Service] Plausib.
Warning
The output switches if extrapolated measured values are to be output for
implausible measured values see table 21, page 44, ErrRej.
This may be caused by an internal error, hardware errors, obstruction of
the light beam, optical interference or electrical interference.
Options
off
on
Factory setting
on
[MF2 Service] Not
Ready
The output switches when the device is not ready for operation. Possible
causes could be hardware errors, optical or electrical interference or
a deactivated laser diode. This warning message is also issued during
initialization.
Options
off
on
Factory setting
on
[MF2 Service] Heating
Status
The output switches if the internal device heater is in operation.
Options
off
on
Factory setting
on
10.3.11 Module 22: Setup Preset Static
Type
Configuration module, no input and output data
Description
This module is used to set the reference value for the static preset via digital input MF1
see "MF1 – Preset submenu", page 42.
NOTE
If module 5 Distance/i2w, Preset Dyn./o2w is also loaded, the static preset value is
overwritten by the dynamic preset value from the input data of module 5.
10 PROFINET IO INTERFACE
72
O P E R A T I N G I N S T R U C T I O N S | DL100 Pro PROFINET 8015069/19H9/2021-10-15 | SICK
Subject to change without notice