Table 31: MF2 module parameters
Name Description
Function MF2 Select function for MF2 output.
Options
•
[Output] Distance Threshold: Output is switched when the distance has
been overwritten from the module parameter [MF2 Distance] threshold.
•
[Output] Speed Threshold: Output switches when the speed limit from
the [MF2 Speed] Threshold module parameter has been exceeded. The
direction is set in the [MF2 Speed] Mode module parameter.
•
[Output] Service: The output switches if at least one of the service bits
selected under [MF2 Service] Laser Warning...[MF2 Service] Heating has
been set.
Factory setting
•
[Output] Distance Threshold
[MF2] Active State Select the active level or signal edge of the MF2.
Options
•
low
•
High
Factory setting
•
low
[MF2 Distance] Thresh‐
old [mm]
Enter the distance threshold value.
Options
•
-300,000 ... 300,000 [mm]
Factory setting
•
1,990 [mm]
[MF2 Distance] Hyste‐
resis [mm]
Enter the distance threshold hysteresis.
Options
•
1 ... 300,000 [mm]
Factory setting
•
10 [mm]
[MF2 Speed] Threshold
[mm/s]
Enter speed threshold. The switching hysteresis is fixed at 100 mm/s.
Options
•
0 ... 15,000 [mm/s]
Factory setting
•
5,000 [mm/s]
[MF2 Speed] Mode Select direction for detecting the speed overrun.
Options
•
negative direction [-]
•
positive direction [+]
•
both directions [+/-]
Factory setting
•
both directions [+/-]
[MF2 Service] Laser
Warning
The output switches when the aging of the laser diode means that the
device is nearly due to be replaced.
Options
•
off
•
on
Factory setting
•
on