3. Open the device name > Password > Reset Service password.
The Reset password window appears.
4. Click Next.
5. Enter the code sent by SICK.
6. Click Ok.
Password has been reset to the default password servicelevel. Parameters are
not changed.
Assigning a new password for the Service user level
1. Open SOPASET.
2. Log on to the device with the Service user level and the default password
servicelevel.
3. Open the device name > Password > Change password.
4. Assign the new password for the Service user level.
6.5.4 Display of the current operational status
The Field Evaluation Monitor page (in the navigation area of the device window, below the
Monitor node) displays the current operational status consisting of measurement data,
status of the individual fields as well as status of the digital inputs and digital outputs.
The field monitor, which is located in the middle of the page, displays measurement
data as blue points and/or a blue line. Occupied fields are shown in yellow; free fields
appear in green.
6.5.5 Changing parameters
WARNING
Risk of injury/risk of damage due to incorrect parameters!
Parameter changes are transferred to the device and take effect immediately after
being edited. Permanent saving (in the non-volatile memory of the device) does
not occur, however, until the Save permanent button is clicked.
Correct transmission of the parameters must be checked for each device, e.g. by
testing in the application. A new test is required each time the parameters are
changed.
After parameter changes, the effectiveness of the protective device in the applica‐
tion must be reviewed and documented.
Before beginning the parameterization, ensure that the machine, plant or applica‐
tion in which the device is involved as part of a safety function is in a safe state.
Please note:
The individual parameters of the device can be changed on the pages below the
Parameters node in the navigation area.
The device for safety-related applications must be configured/parameterized using the
SOPAS ET configuration software.
6.5.6 Default configuration
The product is delivered with the following parameterization, which prevents uninten‐
tional or inadvertent activation of the sensor. The device has this default parameteriza‐
tion in the delivery condition.
COMMISSIONING AND CONFIGURATION 6
8022483/1LM2/2024-03-27 | SICK O P E R A T I N G I N S T R U C T I O N S | TiM361S
29
Subject to change without notice