NOTE
The device has a diagnostic coverage (DC) of zero in accordance
with EN ISO 13849-1:2015 PL b, i.e., it is not required to detect errors, and if they
do occur, they can result in loss of the safety function.
The downstream controller, for example, can be used to detect errors by means of
testing and diagnostic measures.
7.4 Fault exclusions
No fault exclusions have been specified for the device. The occurrence of faults can
result in the loss of the safety function.
7.5 Manipulation
The device does not have any protective measures against manipulation, especially
none that relate to the optical system. Objects, especially covering objects on the optics
cover and/or in the blind zone, are not detected by the device, causing impairment,
reduction or complete loss of detection capability, and the device no longer being able
to perform the safety function.
Manipulations with effects similar to undetected errors (see "Undetected errors and
faults", page 43) are also not detected.
7 ERROR BEHAVIOR
44
O P E R A T I N G I N S T R U C T I O N S | TiM361S 8022483/1LM2/2024-03-27 | SICK