Technical specifications
Minimum Typical Maximum
5 V AC 230 V AC 253 V ACSwitching voltage AC
Electrical endurance output modules UE410-2RO/
UE410-4RO
5 V DC 230 V DC 253 V DCSwitching voltage DC
Maximum DC current
UE410-2RO/UE410-4RO
Switching current 10 mA 6 A
Minimum contact load
with U
n
= 24 V DC
50 mW
Total current 8 A
Response time
32)
30 ms
Type of output Floating N/O contacts, positively guided
Contact material AgSnO
2
Output circuit fusing 6 A (gG), per current path
AC-15: U
e
250 V, I
e
3 AUsage category
DC-13: U
e
24 V, I
e
3 A
32)
Time from LOW on B1/B2 to relay drop-out.
250 V AC resistive load
on 1 N/O contact
Switching current [A]
Operations
Resistive load
DC current [A]
DC voltage [V DC]

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK UE410-MU and is the answer not in the manual?

SICK UE410-MU Specifications

General IconGeneral
Operating Voltage24 V DC
Safety outputs2
Response time≤ 20 ms
Protection classIP20
Housing materialPlastic
Safety Integrity LevelSIL 3
Performance LevelPL e
Number of Outputs2
MountingDIN rail
Supply voltage24 V DC
Current consumption≤ 100 mA
Output typeSemiconductor
Switching current≤ 0.5 A
ConnectionScrew terminals