Siemens 8DJH - Switching the Three-Position Disconnector from OPEN to EARTHED Position

Siemens 8DJH
121 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation
102/121 Revision 05 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DJH 500-8067.9
Switching to OPEN
position
Insert the operating lever and turn counter-
clockwise as far as it will go.
The position indicator of the disconnector
shows the OPEN position.
The three-position disconnector is open.
Final activities Remove the operating lever.
The control gate returns to its initial
position.
Fit the padlock (optional) on the locking
device in the desired position (see page 87,
"Mechanical interlocking with padlock").
19.6 Switching the three-position disconnector from OPEN to EARTHED position
Preconditions Circuit-breaker in OPEN position
Three-position disconnector in OPEN position
Check service readiness (see page 85,
"Ready-for-service indicator").
Verify safe isolation from supply of the
feeder (see page 104, "Verification of safe
isolation from supply").
Remove the padlock (optional) from the
locking device of the three-position
disconnector.
Releasing the actuating
opening
Push the control gate of the three-position
disconnector downwards, and hold it.
The actuating opening of the earthing
switch is open.
Switching to EARTHED
position
Insert the operating lever and turn clockwise
as far as it will go.
The position indicator of the earthing switch
shows the EARTHED position.
Final activities Remove the operating lever.
The control gate returns to its initial
position.
Fit the padlock (optional) on the locking
device in the desired position (see page 87,
"Mechanical interlocking with padlock").