500-8067.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DJH • Revision 05 27/121
Description
8.2 Three-position switch-disconnector
Switching capacity for switch-disconnectors according to IEC/EN 62271-103 / VDE 0671-103
Switching capacity for make-proof earthing switches according to
IEC/EN 62271-102 / VDE 0671-102
Switching capacity for switch-fuse combination according to IEC 62271-105 / VDE 0671-105
Switching capacity for make-proof earthing switches (with HV HRC fuses-links on feeder side)
Rated voltage U
r
kV 7.2 12 15 17.5 24
Test duty TD
load
Rated mainly active load-
breaking current I
load
100 operations I
load
[I
1
]A 630
20 operations 0.05 I
load
[I
1
]A 31.5
Test duty TD
loop
Rated closed-loop breaking current I
loop
[I
2a
]A 630
Test duty TD
cc
Rated cable-charging breaking current I
cc
[I
4a
]A 68
Test duty TD
Ic
Rated line-charging breaking current I
Ic
[I
4b
]A 68
Test duty TD
ma
Rated short-circuit making current
I
ma
50 Hz up to
kA
63
50/52.5
1
1
Design option
60 Hz up to
kA
65
52/55
1
Test duty TD
ef1
Rated earth-fault breaking current I
ef1
[I
6a
]A 200
Test duty TD
ef2
Rated cable-charging breaking current and
rated line-charging breaking current under
earth-fault conditions
I
ef2
[I
6b
( 3 · I
4a
)
or I
6b
( 3 · I
4b
)]
A115
Number of mechanical operating cycles / Classification n 1,000 / M1
Number of electrical operating cycles with I
load
/ Classification n 100 / E3
Number of short-circuit making operations with I
ma
/ Classification n 5 / E3
C-classification For switch-disconnectors (no restrikes, TD: I
cc
, I
Ic
)C2
Rated voltage U
r
7.2 12 15 17.5 24
Rated short-circuit making current I
ma
50 Hz up to kA 63
50/52.5
1
1
Design option
60 Hz up to kA 65
52/55
1
Number of mechanical operating cycles / Classification n 1000 / M0
Number of short-circuit making operations / Classification n 5 / E2
Rated voltage U
r
kV 7.2 12 15 17.5 24
Rated normal current I
r
A
200
1
1
Depending on HV HRC fuse-link
Rated transfer current I
transfer
A
1500 1300
Maximum transformer rating kVA 1000 1250 1600 1600 2000
Tripping time for striker operation ms 50 ms
Tripping time for release operation ms 130 ms
Setting time for delay at the protection device ms 100 ms
Rated voltage U
r
kV 7.2 12 15 17.5 24
Rated short-circuit making current I
ma
50 Hz kA 6.3
60 Hz kA 6.5
Rated short-time withstand current I
k
with t
k
= 1 s kA 2.5