500-8067.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DJH • Revision 05 37/121
Description
8.11 Selection of HV HRC fuse-links
Note to HV HRC fuse-links According to IEC 60282-1 (2009) Clause 6.6, the breaking capacity of HV HRC fuse-links is
tested within the scope of the type test at 87% of their rated voltage.
In three-phase systems with resonance-earthed or isolated neutral, under double earth fault
and other conditions, the full phase-to-phase voltage may be available at the HV HRC fuse-link
during breaking. Depending on the size of the operating voltage of such a system, this applied
voltage may then exceed 87% of the rated voltage.
To be observed during configuration of switching devices and selection of HV HRC fuse-links:
Use only fuse-links satisfying the stated operating conditions.
Use only fuse-links whose breaking capacity was tested at least with the maximum system
voltage.
In case of doubt, select a suitable HV HRC fuse-link together with the manufacturer.
Allocation of HV HRC fuses and transformers
The three-position switch-disconnector in the transformer feeder (transformer switch) was
combined with HV HRC fuse-links and tested in accordance with IEC 62271-105.
The following transformer protection table shows HV HRC fuse-links tested by Siemens, which
are recommended for transformer protection.
The protection table applies to:
Maximum ambient air temperature in the switchgear room of 40 °C according to
IEC 62271-1 considering the influence of the switchgear enclosure
Requirements according to IEC 62271-105
Protection of distribution transformers according to IEC 60787
Rated power of transformer (no overload operation)
The specified HV HRC fuse-links make SIBA are type-tested back-up fuses according to
IEC 60282-1. The dimensions conform to DIN 43625.
The HV HRC fuse-links have a thermal protection in form of a temperature-limiting striker
tripping operating in case of defective HV HRC fuse-links or high overload currents.
Please contact your regional Siemens representative if you want to use HV HRC fuse-links from
other manufacturers.
Basis for selection of HV HRC fuse-links:
IEC 60282-1
IEC 62271-105
IEC 60787
Recommendations and data sheets of fuse manufacturers
Permissible power loss in the switchgear enclosure at an ambient air temperature of 40° C
ATTENTION
Please use only fuses tested by Siemens, which are listed in the following fuse tables.
The use of other fuse types must be checked by Siemens in advance. Please contact the
regional Siemens representative.