500-8067.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DJH • Revision 05 107/121
Operation
Indicatio
n
VOIS+, VOIS R+ CAPDIS-S1+ CAPDIS-S2+ Description of the indication
L1 L2 L3 L1 L2 L3 L1 L2 L3 State of the
relay contacts
1
Red Green
A0 U 0 U = 0 Operating voltage not present.
A1 U 0 U = 0 Operating voltage present.
A2 U 0 U = 0 Operating voltage not present.
Auxiliary voltage not available (only CAPDIS-S2+).
A3 U 0 U = 0 Failure in phase L1, operating voltage at L2 and L3 (for
CAPDIS-Sx+ also earth-fault indication).
A4 - U 0 U = 0 Voltage (not operating voltage) present.
A5 - U 0 U = 0 Indication: "Test" passed (lights up shortly).
A6 - U 0 U = 0 Indication: "Test" not passed (lights up shortly).
A7 - U 0 U = 0 Overvoltage present (lights up permanently).
A8 - - U 0 U = 0 Indication: "ERROR" e.g. in case of missing auxiliary voltage.
1
LED does not light up, LED lights up