EasyManua.ls Logo

Siemens 8DJH - Page 31

Siemens 8DJH
121 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
500-8067.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DJH • Revision 05 31/121
Description
Releases Releases trip the circuit-breaker. The electrical opening command is transmitted to the OPEN
latch via a magnet armature by unlatching an energy store. Depending on the operating
mechanism used, up to 2 releases can be used.
Shunt release (-Y1) Shunt releases are used to trip or electrically open circuit-breakers. The opening command is
executed by application of an auxiliary voltage (AC or DC, depending on the design option).
After opening the circuit-breaker, the release is de-energized internally.
Undervoltage release
(-Y7)
Undervoltage releases are used to trip or electrically open circuit-breakers. During normal
operation, the shunt releases are supplied with a closed-circuit current from an auxiliary
voltage source (DC or AC, depending on the design option). When the auxiliary voltage falls
below a specific value, or when it is interrupted, the opening operation takes place.
C.t.-operated release (-Y6) The low-energy c.t.-operated release 3AX1104 (-Y6) is used for protection devices with a
pulse output, which are supplied with instrument transformer current. The tripping circuit is
supplied as well through the protection core of the current transformer. When a pulse of
0.1 Ws runs through the tripping circuit, the opening operation takes place.
Low-energy release (-Y6) The low-energy release (-Y6) is provided for use in combination with the transformer monitor
IKI-30 (make Kries) or the protection device 7SJ45 (make Siemens) supplied with instrument
transformer current. The tripping circuit is supplied through the current sensor or current
transformer. When a pulse of 0.02 Ws runs through the tripping circuit, the opening operation
takes place. The low-energy release is available for the vacuum circuit-breaker type 2.
Varistor module The varistor module limits switching overvoltages caused by tripping coils in circuits and
auxiliary circuits. The varistor module is integrated in the releases.
Circuit-breaker tripping
signal
When the circuit-breaker is tripped by a release (e.g. by protection tripping), there is a signal
through the NO contact -S6. If the circuit-breaker is tripped with the mechanical pushbutton,
this signal is suppressed by the NC contact -S7.
Power consumption of the operating coils
Operating coil Power consumption [W/VA]
Circuit-breaker type 2
Closing solenoid (Y9) 370
Shunt release (Y1) 370
C.t.-operated release (Y6) 30
Low-energy current release (Y6) 10
Undervoltage release (Y7) 20

Table of Contents

Other manuals for Siemens 8DJH

Related product manuals