500-8067.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DJH • Revision 05 65/121
Installation
Optionally: Mount voltage sensors (see page 72, "Installing voltage sensors").
Carefully coat the push-on surfaces (high-quality joints) of the cable plugs and the bushings
with the delivered mounting paste (see scope of supply of the cable plugs).
Push the cable plugs ① to ③ onto the bushings and mount them according to the
manufacturer’s instructions. Observe the phase sequence.
NOTE: A too high torque can cause damage to the bushing. Tighten the cable plug with a
torque according to the manufacturer's instructions (max. 50 Nm).
Mount the upper part of the cable clamps ⑥ .
Align the cable bracket and bolt it tight.
Refit the cross member, see page 77, "Removing and mounting the cross member".
Connect the earthing cables of the plug housings and the cable shield at the cross
member .
Hook the cable compartment cover in again, see page 76, "Removing and mounting the
cable compartment cover".
The cable connection is completed.
Double cables and surge
arresters
Double cables and surge arresters can be connected to the following panel types using the
corresponding plug-in cable systems:
Ring-main panel
Cable panel
Circuit-breaker panel
Please observe the following:
Depending on their type, double cable connections require a deep cable compartment cover
and larger floor openings.
Depending on their type, surge arresters also require a deep cable compartment cover.
For further information, see page 16, "Cable connection".