500-8067.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DJH • Revision 05 73/121
Installation
➭ Mount the cable plugs according to the manufacturer's instructions. Do not mount the
sealing stopper of the cable plug.
➭ Clean the cone of the voltage sensor and the cable plug with a lint-free wiping cloth.
➭ Coat the cone of the voltage sensor with the mounting paste recommended by the plug
manufacturer.
➭ Screw the voltage sensor into the cable plug at the cast-resin hexagon ① .
Fig. 48: Mounting the voltage sensor (example)
➭ Mount the earthing cable at the earthing connection ② , and connect it to the cross
member.
➭ Connect the measuring lead ③ with the connection cables.
➭ If they have not been pre-assembled at the factory, lead the connection cables of the
voltage sensors through the cable tube upwards into the low-voltage compartment or the
operating mechanism compartment. Connect according to the circuit diagram. For wire
routing, see page 71, "Installing ring-core current sensors at the cable connection".