500-8067.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DJH • Revision 05 73/121
Installation
Mount the cable plugs according to the manufacturer's instructions. Do not mount the
sealing stopper of the cable plug.
Clean the cone of the voltage sensor and the cable plug with a lint-free wiping cloth.
Coat the cone of the voltage sensor with the mounting paste recommended by the plug
manufacturer.
Screw the voltage sensor into the cable plug at the cast-resin hexagon ① .
Fig. 48: Mounting the voltage sensor (example)
Mount the earthing cable at the earthing connection ② , and connect it to the cross
member.
Connect the measuring lead ③ with the connection cables.
If they have not been pre-assembled at the factory, lead the connection cables of the
voltage sensors through the cable tube upwards into the low-voltage compartment or the
operating mechanism compartment. Connect according to the circuit diagram. For wire
routing, see page 71, "Installing ring-core current sensors at the cable connection".