&RPPLVVLRQLQJ
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
9-20 A5E00105492-03
7ULJJHUFRQGLWLRQ
The "Trigger condition for monitoring" determines whether to update values
once when the trigger point is reached or continuously every time the trigger
point is reached.
The "Trigger condition for controlling" determines whether to assign control
values once or permanently to the variable to be controlled.
You can customize the trigger points using the tool "Monitor and control variable" in
menu item 9DULDEOH!6HW7ULJJHUstart.
6SHFLDOIHDWXUHV
If "Trigger condition for monitoring" is set to RQFH, the menu items 9DULDEOH!
8SGDWHVWDWXVYDOXHor9DULDEOH!0RQLWRU have the same effect, namely a
single update.
If "Trigger condition for controlling" is set to RQFH, the menu items 9DULDEOH!
8SGDWHFRQWUROYDOXHor9DULDEOH!&RQWURO have the same effect, namely a
one-time assignment.
If trigger conditions are set toSHUPDQHQW, the said menu items have different
effects as described above.
If monitoring and controlling is set to the same trigger point, monitoring is
executed first.
With some CPU versions (e.g. CPU 314-1AE03) values are not assigned at
every cycle when SHUPDQHQWFRQWUROis set.
Remedy: Use the testing function)RUFH.
6DYLQJ2SHQLQJWKH9DULDEOH7DEOH
6DYLQJWKH9$7
1. After you abort or complete a test phase, you can save the variable table to
memory. The name of a variable table starts with the letters VAT, followed by a
number from 0 to 65535; e.g. VAT5.
2SHQLQJWKH9$7
1. Select the menu item 7DEOH!2SHQ.
2. Select the project name in the2SHQdialog.
3. In the project window below, select the relevant program and mark the %ORFNV
container.
4. In the block window, select the desired table.
5. Confirm with2..

Table of Contents

Other manuals for Siemens CPU 313C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 313C and is the answer not in the manual?

Siemens CPU 313C Specifications

General IconGeneral
MPI InterfaceYes
Number of digital inputs24
Number of digital outputs16
Number of analog inputs4
Number of analog outputs2
Supply voltage24 V DC
High-speed countersYes
Bit Operations Execution Time0.1 µs
Word Operations Execution Time0.2 µs
Power Consumption5 W
Dimensions (W x H x D)40 x 125 x 130 mm
Operating Temperature0 to 60 °C
Communication InterfacesMPI
Programming LanguagesLAD, FBD, STL
Product type designationCPU 313C
Weight490 g

Related product manuals