&RQILJXULQJ
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
A5E00105492-03
5-39
:LULQJEXVFDEOHV
When wiring PROFIBUS cables, you must not
twist,
stretch
or compress them.
When wiring indoor bus cables, also maintain the following marginal conditions
(d
A
= outer cable diameter):
Table 5-20 Marginal conditions for wiring interior bus cables
&KDUDFWHULVWLFV &RQGLWLRQ
Bending radius (one-off) 80 mm (10 x d
A
)
Bending radius (multiple times) 160 mm (20 x d
A
)
permitted temperature range during installation -5 °C to +50 °C
Shelf and stationary operating temperature range -30 °C to +65 °C
&URVVUHIHUHQFH
If you want to use fiber optic cable cables for PROFIBUS, you can find further
information on this topic in the SIMATIC NET, PROFIBUS Networks Manual.
56EXVFRQQHFWRU
Table 5-21 Bus connector
7\SH 2UGHU1R
RS485 bus connector, up to 12 Mbps,
with 90° cable exit,
without PG interface,
with PG interface
6ES7 972-0BA11-0XA0
6ES7 972-0BB11-0XA0
Fast Connect RS485 bus connector, up to 12 Mbps,
with 90° cable exit, with insulation displacement technology
, without PG interface,
with PG interface
6ES7 972-0BA50-0XA0
6ES7 972-0BB50-0XA0
RS485 bus connector up to 12 Mbps
with 35° cable exit (not for CPU 31xC, 312, 314, and 315-2
DP
without PG interface
with PG interface
6ES7 972-0BA40-0XA0
6ES7 972-0BB40-0XA0
$SSOLFDWLRQ
You require these bus connectors to connect the PROFIBUS cable to an MPI or
PROFIBUS-DP interface
You do QRW require a bus connector for:
DP slaves with degree of protection IP 65 (e.g. ET 200C)
RS485 repeater.

Table of Contents

Other manuals for Siemens CPU 313C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 313C and is the answer not in the manual?

Siemens CPU 313C Specifications

General IconGeneral
MPI InterfaceYes
Number of digital inputs24
Number of digital outputs16
Number of analog inputs4
Number of analog outputs2
Supply voltage24 V DC
High-speed countersYes
Bit Operations Execution Time0.1 µs
Word Operations Execution Time0.2 µs
Power Consumption5 W
Dimensions (W x H x D)40 x 125 x 130 mm
Operating Temperature0 to 60 °C
Communication InterfacesMPI
Programming LanguagesLAD, FBD, STL
Product type designationCPU 313C
Weight490 g