7HVWLQJ)XQFWLRQV'LDJQRVWLFVDQG)DXOW(OLPLQDWLRQ
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
11-18 A5E00105492-03
$VVXPSWLRQVUHJDUGLQJWKH67(3XVHUSURJUDP
For this 67(3 user program it is assumed that:
Diagnostic data for the input module at address 200
H
is to be read.
Data record 1 is to be read out.
Data record 1 is to be stored in DB 10.
67(3XVHUSURJUDP
67/ 'HVFULSWLRQ
CALL SFC 59
REQ :=TRUE
IOID :=B#16#54
LADDR:= W#16#200
RECNUM :=B#16#1
RET_VAL :=MW2
BUSY :=MO.0
RECORD :=P# DB10.DBX 0.0 BYTE 240
//Request to read
//Identifier of the address area, here the I/O input
//Logical address of the module
//Data record 1 is to be read
//An error code is output if an error occurs
//Read operation not finished
//DB 10 is target area for the read data record 1
1RWH
Data is only returned to the target area if BUSY is reset to 0 and if no negative
RET_VAL has occurred.

Table of Contents

Other manuals for Siemens CPU 313C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 313C and is the answer not in the manual?

Siemens CPU 313C Specifications

General IconGeneral
MPI InterfaceYes
Number of digital inputs24
Number of digital outputs16
Number of analog inputs4
Number of analog outputs2
Supply voltage24 V DC
High-speed countersYes
Bit Operations Execution Time0.1 µs
Word Operations Execution Time0.2 µs
Power Consumption5 W
Dimensions (W x H x D)40 x 125 x 130 mm
Operating Temperature0 to 60 °C
Communication InterfacesMPI
Programming LanguagesLAD, FBD, STL
Product type designationCPU 313C
Weight490 g