2BStructure and function
17BS-LINE and C-LINE
3
25 |
138
Building Technologies
007004_t_en_--
Fire Safety
2015-11-04
3.2.2 S-LINE
Properties
In contrast to C-LINE detectors, S-LINE detectors have the following features:
Dynamic influence on the parameter sets
Pattern recognition
Real time interpretation of the situation
Process- and time-controlled switchover of the parameter sets
Signal processing of the S-LINE detectors is based on ASA
technology
(ASA =
Advanced Signal Analysis).
ASA
technology
can also be characterized as "second
generation algorithms". Signal processing with
ASA
technology
allows for optimum
adaptation of detector behavior to the corresponding ambient conditions.
S-LINE detectors are characterized by their unique detection reliability and high
immunity to deceptive phenomena.
Operating mode: Signal processing with ASA
technology
The following figure shows signal processing with S-LINE detectors in the form of a
diagram.
Sensory
The signals captured by the sensory are transmitted to the algorithm. The
algorithms are set by selecting the parameter set.
Algorithms
In comparison to the detection algorithms (DA), the individual parameters of the
selected parameter set can be adapted with
ASA
technology
. A real time
interpretation of the situation leads to a dynamic influence on the algorithm. This
results in a broadening of the application range of the parameter set and thus of
the detector. The detector reacts more sensitively in the event of fire, and more
robustly in the event of deceptive phenomena.
Switching over the parameter set
In addition to the selection of the parameter set, the S-LINE detectors enable time-
or process-controlled switching over of the parameter sets ('Manned'/'Unmanned'
switchover). Thanks to this function, the detector can be used in places where the
situation changes regularly and frequently (e.g. kitchens, production halls).
C
Dynamic influence
of parameter
Environment
Evaluation of the
situation
Danger
level
Result
Algorithms
Signal analysis
Sensory

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FDOOT241-A3 and is the answer not in the manual?

Siemens FDOOT241-A3 Specifications

General IconGeneral
BrandSiemens
ModelFDOOT241-A3
CategoryFire Alarms
LanguageEnglish

Related product manuals