26BParameter sets: Wide-spectrum smoke detector
| 138
2015-11-04
4.4.1.3 Specifications
2 Robust 70 2.8
1 Universal 50 2.0
3 Sensitive 30 1.4
14 Application-specific parameter sets
15
All parameter sets apart from 14 and 15 comply with standard EN 54-7.
4.4.2 Wide-spectrum smoke detector FDO221
4.4.2.1 Description
Parameter sets:
Standard (2)
The parameter set displays robust behavior in rooms where deceptive phenomena
such as cigarette smoke can be expected.
Standard Plus (3):
The parameter set reacts in a fast and highly sensitive manner. It is especially
suited for rooms without deceptive phenomena, where the priority is on detecting
the fire as early as possible.
4.4.2.2 Use
Risk of damage to
persons
2 Standard
3 Standard Plus