29BTechnical Ambient Supervision Message
| 138
2015-11-04
in interactive mode:
● As DO1151A/DO1152A Universal
● As DO1153A Ultra Sensitive
● As DO1151A/DOT1152A Balanced
● As DT1152A A1R
in MS8 mode:
● Sensor mode 0 (neural fire detector) Sensitive
● Sensor mode 1 (heat detector) A1R
● Sensor mode 2 (smoke detector) Universal
Standard
Robust
Standard
A1R
A1R
Upon commissioning of the fire detection system, the optimum parameter set must
be selected based on the existing risk and the ambient conditions.
If the fire detectors are operated on the FDnet (addressed), the fire detectors are
automatically set to the basic setting for the country in question when the control
panel is started up for the first time. Individual adaptation takes place using the
commissioning software on the corresponding control panel.
If the fire detectors are operated in collective, MS8, SIGMALOOP, or AnalogPLUS
mode, the detectors operate with the default setting the first time they are
commissioned. In this operation mode, individual adaptation of the detector
behavior is performed using the detector exchanger and tester FDUD292.
4.7 Technical Ambient Supervision Message
The system is not controlled as laid down in EN 54-2
Infringement of the EN 54-2 standard
● According to EN 54-2, signals for temperature detection must not be used to
control fire detection equipment.
The 'Technical Ambient Supervision Message' cannot be configured on all fire
control panels. Observe the information in the 'List of compatibility'.
See also
Applicable documents [➙ 9]