3BPlanning
26BParameter sets: Wide-spectrum smoke detector
4
65 |
138
Building Technologies
007004_t_en_--
Fire Safety
2015-11-04
4.4 Parameter sets: Wide-spectrum smoke detector
4.4.1 Wide-spectrum smoke detector FDO241
4.4.1.1 Description
Parameter sets:
Robust (2)
The parameter set displays robust behavior in rooms where deceptive phenomena
such as cigarette smoke can be expected.
Universal (1)
The sensitivity and response time of this parameter set are between those of the
'Robust (2)' and 'Sensitive (3)' parameter sets.
Sensitive (3)
The parameter set reacts in a fast and highly sensitive manner. It is especially
suited for rooms without deceptive phenomena, where the priority is on detecting
the fire as early as possible.
Download 1 (14)/Download 2 (15)
The parameter sets can be loaded on site on an application-specific basis
(depending on the control panel).
4.4.1.2 Use
No.
Name
Risk of damage to
persons
Value
concentration
Room geometry
Deceptive
phenomena
Risk of fire
Critical fire size
Low…
High
Low…
High
Simple…
Complex
Few…
Many
Low…
High
Low…
Medium
2 Robust
1 Universal
3 Sensitive