'No deviation' Normal, no fault is present
The detector is fully functional
None
'maybe excha.'
1
Observe information
The detector is fully functional
For
:
Slightly soiled
Clarify cause during periodic maintenance
'advice excha.'
1
Replacement recommended
Detector is still functional, in spite of minor
problems
For
:
Average soiling
Untypical sensor values caused by
environmental influence
For
:
Average soiling
Remedy the cause during the next
maintenance
Replace detector if necessary
'needed excha.'
1
Replacement necessary
Detection possibly restricted; alarming is still
possible
For
:
Heavily soiled, failure of one optical sensor
Failure of one or both thermal sensors
For
:
Heavily soiled
Perform maintenance service
Replace detector