6.6 Limitation of repetitions
Depending on program module, see User Documentations.
6.6.1 Repetition in case of loss of flame
If the flame is lost during operation, a maximum of 1 repetition per controlled startup
can be performed via the control thermostat or pressurestat, or else a non-alterable
lockout will be initiated.
6.6.2 Repetition in case of no flame is established by the end of
safety time (TSA)
If no flame is established by the end of the safety time, a maximum of 3 repetitions per
controlled shutdown are possible.
With repetitions from the operating position (loss of flame), the flame must have been
established on completion of the safety time, or else a non-alterable lockout will be
initiated.