98/106
Building Technologies Basic Documentation LME7... CC1P7105en
15 Operation via internal LED 17.04.2018
15.6 First startup with a new program module or
in case of replacement of program module
Alternately
Display shows alternately rSt and PrC.
Display shows the replacement of the program module.
Signal lamp blinks red once and yellow twice alternately.
nfo
>3 s
Press
nfo
for >3 seconds to start data download from the
program module.
Signal lamp blinks yellow.
The process of 3 seconds is supported by a short flash of
the yellow signal lamp.
Note:
If you press
nfo
for <3 seconds, data download does not
start. To start the restore process again, the LME7 must be
reset by switching mains ON/OFF.
Display shows run during download (restore process) of the
program sequence.
Alternately
Display shows alternately End and rSt.
Display shows the end of data exchange.
Signal lamp blinks red.
After 2 minutes, the unit changes to Loc 138
Β
LCD Bild 06/0908
Alternately
After the restore process, the unit is automatically in
the lockout position (LOC 138) and must be reset for
operation!