13.9.2 Parameters without index, with no direct display
13.9.2.1. Example of parameter 224 (specified time air pressure switch) on the
parameter level
P
Vh
min
s%
Bild172/1107
Press for specified time for air pressure
signal.
Display: Parameter 224: blinks, characters
._._
do not.
/reset
P
Vh
min
s%
Bild173/1107
Press
/reset
for editing mode.
Display: 48.510
or
P
V
h
min
s
%
Bild 174/1107
Press or to shift the former specified
time to change mode one place to the left.
Display: Specified time 48.510 blinks.
Note
To detect display errors, the value appears
one place shifted to the left.
or
P
V
h
min
s
%
Bild 175/1107
Press or to set the specified time.
Display: Specified time 53.361 blinks.