96/106
Building Technologies Basic Documentation LME7... CC1P7105en
15 Operation via internal LED 17.04.2018
A
>3 s
Alternately
Press
 for >3 seconds to display alternately LoA and
41.
The relative value 41 of the current position or current
speed is displayed.
Actuator position 0°
0 ς potentiometer value =
0% display
Actuator position high-fire
>0°
<90° = potentiometer value
>0 ς <1000 ς = 100%
display
Current speed
0 rpm = 0% display
Current speed corresponds
to the rated load speed =
100% display
The actual value (example 41%) is displayed and the signal
lamp blinks green.
Example: Position of actuator or the current speed 41%
(based on range between high-fire and 0° or 0 rpm)
A
and
+
or
-
Press
A
 simultaneously with
+
 or
-
 to adjust the
actuator position or the fan speed between low-fire (x%) and
high-fire (100%).
Release the buttons when the required position or speed is
reached.
Signal lamp blinks s green.
Example: Value 43
Alternately
Display shows alternately LoA and 43.
Signal lamp blinks green.
Example: Required position of actuator or current speed
43%
-
and
+
Press
 and
 simultaneously (Escape) to return to
normal operation.
Display: oP
When manual adjustment is completed, the actuator or the
PWM fan returns to the analog preset output!