Application planning
4
4.1
General installation guidelines
General installation guidelines
The following guidelines must be observed when mounting and connecting the CMK2000:
When connecting the CMK2000, make sure that you observe all applicable and legally
binding standards. Adhere to the relevant national and regional regulations when
installing and operating the device. Check with the local authorities regarding the
standards and rules to be followed in your particular case.
Ensure a zero-voltage state during assembly and connection work.
4.2
Installation location
Selection of the installation site / mounting position
The device can be mounted on a standard mounting rail or on a wall.
Permissible installation positions: horizontal or vertical
Ensure that the permissible ambient temperature range is observed:
Horizontal installation: 0 °C to 55 °C
Vertical installation: 0 °C to 45 °C
Ensure that condensation is not produced at a relative humidity between 10% and 95%.
Ensure that the atmospheric pressure is between 795 hPa and 1080 hPa.
Observe sufficient clearance above and below (minimum 35 mm). Provide sufficient
space for the power supply, Ethernet and KNX bus connections.
Table 4- 1 Device dimensions
CMK2000 dimensions
Width 72 mm
Height
90 mm
Depth
60 mm (incl. protrusions)