Configuring and commissioning using ETS
8.6 Transfer of data from LOGO! to KNX
CMK2000
52 Operating Instructions, 11/2015, A5E34877550B/001
Transfer of data from LOGO! to KNX
8.6.1
Overview
Data transfer from LOGO! to KNX
The CMK2000 allows the transfer of simple digital values. In addition, the linking of two
digital values is used which are defined in KNX as "Key operation with two independent
keys" (2-bit).
Parameter assignment in
the ETS tool
Normal 1 bit The output information of
the LOGO! 8 CPU is
mapped 1:1 to the KNX
DPT 1.xxx Transfer of 1-bit values
(Page 55)
Dimming
1 bit Switch over (brief pressing
DPT 1.001 Dimming (1 bit)
(Page 56)
Dim brighter/darker (long
DPT 3.007
2 bits Switch on/off (brief press-
DPT 1.001 Dimming (2 bits) with
stop message frame
(Page 58)
Dim brighter/darker (long
DPT 3.007
Shutter/blind /
solar protection
1 bit
Solar protection up / down
DPT 1.008 Solar protection control
(1 bit) (Page 59)
Stop or slats open / close
DPT 1.009
2 bits Solar protection up / down
DPT 1.008 Solar protection control
(2 bits) (Page 61)
Slats open/close (brief
DPT 1.009
Percentage
8 bits 1 byte unsigned DPT 5.001 Transferring percentage
Integer value
8 bits
Transferring integer
values (Page 65)
16 bits
32 bits
Float value 16 bits 2 bytes signed DPT 9.xxx Sending float values
Detailed information on the standardized data point types (DPT) can be found at
www.knx.org.