Configuring and commissioning using ETS
8.7 Data transfer KNX to LOGO!
CMK2000
68 Operating Instructions, 11/2015, A5E34877550B/001
8.7.2
Supported KNX data types
You can use the variable memory and the flags of the LOGO! 8 to exchange data with the
KNX bus.
Supported KNX data types
The following data types are supported for the transfer of data from the KNX bus to the
LOGO!:
Image 8-17 Data types KNX to LOGO!
Settings which are always available
All settings are available in the same manner for values in the variable memory and for flags.
If a transferred value is to be saved in the variable memory of the LOGO!, the corresponding
byte address must be specified.
The following byte addresses are possible for variable memories:
1 byte: 0 to 850
2 bytes: 0 to 849
4 bytes: 0 to 847
If a binary value is concerned, this is always saved in the least significant bit (bit 0) of the
specified address.
Image 8-18 Data transfer from KNX to LOGO!: Settings