Configuring and commissioning using ETS
8.7 Data transfer KNX to LOGO!
CMK2000
Operating Instructions, 11/2015, A5E34877550B/001
67
8.7
Data transfer KNX to LOGO!
8.7.1
Overview
Data transfer from KNX to LOGO!
Function
DPT in KNX
Configuration in ETS
Normal
1 bit
The input information
of the KNX bus is
mapped 1:1 to the
input image of
LOGO! 8.
DPT 1.xxx Transfer of 1-bit values
(Page 69)
Digital input with
monoflop response.
DPT 1.xxx Using digital inputs of the
LOGO! 8 as monoflop
(Page 70)
Special function
bus state
1 bit
Digital input directly
indicates the current
KNX bus state.
-- Transfer of KNX bus state
(Page 72)
Percentage
value
8 bits Percentage value DPT 5.001 Transferring percentage
values (Page 73)
Integer value
8 bits
Counter value signed
DPT 6.010
Transferring integer values
(Page 74)
Counter value un-
signed
DPT 5.010
16 bits
2 bytes signed
DPT 8.xxx
2 bytes unsigned
DPT 7.xxx
32 bits
4 bytes signed
DPT 13.xxx
4 bytes unsigned
DPT 12.xxx
Float value 16 bits 2 bytes DPT 9.xxx Sending float values
(Page 75)