Configuring and commissioning using ETS
8.5 Parameter assignments for the KNX channels
CMK2000
Operating Instructions, 11/2015, A5E34877550B/001
51
8.5.6
Response upon loss of KNX bus voltage
The response upon loss of the KNX bus voltage can be set for the communication direction
KNX to LOGO!.
Upon loss of KNX bus voltage
Upon loss of the KNX bus voltage, you can specify whether
the last KNX value is sent to LOGO! or
the value "0" is sent to LOGO!
8.5.7
Response after startup of LOGO!, CMK2000 or KNX
The response of the CMK2000 can be set for the following situations.
Communication direction LOGO! to KNX
After startup of LOGO!, CMK2000 or KNX:
Return of KNX bus voltage
Return of 24 V DC power supply
Return of Ethernet connection to LOGO!
LOGO! in transition from STOP mode to RUN mode
Setting options:
Send current LOGO! value
No action
Communication direction KNX to LOGO!
After startup of CMK2000 or KNX:
Return of 24 V DC power supply
Return of KNX bus voltage
Setting options:
Request current value of KNX
No action