Configuring and commissioning using ETS
8.6 Transfer of data from LOGO! to KNX
CMK2000
56 Operating Instructions, 11/2015, A5E34877550B/001
Special functions: dimming and solar protection
8.6.4.1
This function makes it possible to switch lamps or groups of lamps on and off or to adjust
their dimming using just one bit in the LOGO!.
Image 8-8 Data transfer LOGO! to KNX: Dimming - DPT 1.001 and DPT 3.007
Set a 1-bit LOGO! data type as the preselection for the "Dimming" function:
● Digital input
● Digital flag
● 1-bit variable memory
Two communication objects are provided in the ETS:
● Switch - DPT 1.001 and
● Dimming - DPT 3.007
The configured binary variable can be used for 1-bit dimming. A distinction is made between
short and long setting:
Switch (short setting up to 500 ms) - DPT 1.001
With short setting, the value currently in the switched object (switch over) is inverted and
then sent. The on or off message frame is only generated when the binary value is reset (=
falling edge).