EasyManua.ls Logo

Siemens MICROMASTER 440 Series - Commission Modes

Siemens MICROMASTER 440 Series
117 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Commissioning International English
MICROMASTER 440 Operating instructions
34 6SE6400-5CA00-0BP0
3.2 Commission Modes
The MICROMASTER 440 is supplied with a Status Display Panel (SDP) as the
standard operator panel. Default parameter settings cover the following
requirements:
The motor rating data; voltage, current and frequency data is keyed into the
inverter to ensure that the motor is compatible with the inverter. (A standard
Siemens motor is recommended).
Linear V/f motor speed, controlled by an analogue potentiometer.
Maximum speed 3000 min
-1
with 50 Hz (3600 min-1 with 60 Hz); controllable
using a potentiometer via the inverter’s analogue inputs.
Ramp-up time / Ramp-down time = 10 s.
If more complex application settings are required, please refer to Sections 3.2.4.1
“Quick commissioning (P0010=1)” and 5 “System Parameters” .
Note
Frequency setting; the DIP switch is located on the control board, underneath the
I/O board as shown in Figure 3-2 below. The inverter is delivered as follows:
DIP switch 2:
Off position:
European defaults
(50 Hz, kW etc.)
On position: North
American defaults
(60 Hz, hp etc.)
DIP switch 1:
Not for customer use.
3.2.1 Reset to Factory default
To reset all parameters to the factory default settings; the following parameters
should be set as follows (BOP, AOP or Communication Option needed):
1. Set P0010=30.
2. Set P0970=1.
Note
The reset process can take up to 3 minutes to complete.
Frequency Setting
DIP Switches
Analog Setting
DIP Switches
Figure 3-2 DIP locations on I/O board and the
Control Board
http://nicontrols.com

Table of Contents

Related product manuals