Extended instructions
8.5 Diagnostics (PROFINET or PROFIBUS)
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
357
The following four tables show a binary breakdown of the four bytes of data that are being
analyzed:
Table 8- 136 Example 1: No errors: A value of 0xFFFF_1F00 is returned for MODE 1 (Module
configuration active).
Bit 0 is true; data is available.
Slots 1 (Bit 1) through 20 (Bit 20) contain mo
dules. Slot 21 (Bit 21) and beyond do not contain
modules..
MODE 4 (Module exists) data matches MODE 1 (Module configuration active), so the configured
modules match the existing modules.
Table 8- 137 Example 2: A module has been pulled from PROFINET slave device "et200s_1". A value
of 0x0180_0000 is returned for MODE 2 (Module defective).
Bit 0 is true; data is available.
Only module 15 (Bit 15) is marked as defective. All other modules are functional.
Table 8- 138 Example 2 (continued): A module has been pulled from PROFIBUS slave device
"et200s_1". A value of 0xFF7F_1F00 is returned for MODE 4 (Module exists).
Bit 0 is true; data is available.
Byte 3 0x1F Bit 23 0001-1111 Bit 16
Module 15 (Bit 15) is shown as missing. Modules 1 through 14 (Bits 1 through 14) and 16 through 20
(Bits 16 through 20) are shown as existing.