Approvals, certificates, standards
9.5 XR-300M EEC product group
SCALANCE X-300
226 Operating Instructions, 10/2010, A5E01113043-10
Explosion protection directive (ATEX)
All variants of the XR-300M EEC with 24 V DC power supply meet the requirements of the
EC directive 94/9/EC "Equipment and Protective Devices for Use in Potentially Explosive
Atmospheres".
WARNING
When using (installing) SIMATIC NET products in hazardous area zone 2, make absolutely
sure that the associated conditions are adhered to:
"Approval of SIMATIC/ SIMATIC NET Products for Direct Installation in Ex-Zone 2"
You will find this on the Internet on the pages of Siemens Industry Automation Customer
Support under the following entry ID:
"Entry list" tab > Entry type "Certificates"
ATEX code:
II 3 G Ex nA II T4 KEMA 07 ATEX 0145X
The product meets the requirements of the standards
EN 60079-15 : 2005 (electrical apparatus for potentially explosive atmospheres; Type of
protection "n")
and EN 60079-0:2006
IEC 61850-3 (EN55022 / CISPR22 CLASS A)
The product meets the requirements of the standard IEC 61850-3
(EN55022 / CISPR22 CLASS A).
IEEE 1613
The product meets the requirements of the standard IEEE 1613 CLASS 1 (electrical ports) or
IEEE 1613 CLASS 2 (optical ports).
FM approval
All variants of the XR-300M EEC with 24 V DC power supply meet the requirements of the
standards
Factory Mutual Approval Standard Class Number 3611
FM Hazardous (Classified) Location Electrical Equipment:
Non Incendive / Class I / Division 2 / Groups A,B,C,D / T4 and
Non Incendive / Class I / Zone 2 / Group IIC / T4
Notice for Australia
The product meets the requirements of the AS/NZS 2064 standard (Class A).