Approvals, certificates, standards
9.5 XR-300M EEC product group
SCALANCE X-300
Operating Instructions, 10/2010, A5E01113043-10
229
Device:
SCALANCE
(Variant) c-UL-us c-UL-us
for hazardous
locations
1
FM
1
C-TICK CE ATEX95
Zone 2
1
E1
UL 60950 1
CSA C22.2
No. 60950 1
ANSI / ISA 12.12.01
CSA C22.2 No. 213-
M1987
CL. 1, Div. 2
GP.A.B.C.D T..
CL. 1, Zone 2, GP.
IIC, T..
FM 3611
CL.1, Div.2
GP. A.B.C.D
T..
CL.1, Zone 2,
GP. IIC, T..
Ta:..
AS/NZS
2064
(Class A).
EN 61000-6-4
Class A,
EN 61000-6-2
EN 60079-
15:2005 , EN
60079-0:2006
II 3 G Ex nA II
T..
KEMA 07
ATEX 0145X
-
XR324-4MEEC (1 x 230 V AC,
cable outlet rear)
*) - - ● ● -
XR324-4MEEC (2 x 230 V AC,
cable outlet rear)
*) - - ● ● -
*) Note: UL 508 CSA C22.2 No. 142-M1987
1
For temperature information "T.." or the maximum ambient temperature "Ta:..", refer to the
type plate.
9.5.4 XR-300M EEC mechanical stability (in operation)
The devices of the SCALANCE XR-300M EEC product group meet the following standards
(prerequisite: rack mounted with 4 securing points):
● IEC 60068-2-6
(vibrations during transportation and operation)
Test parameters:
5 – 9 Hz: 3.5 mm
9 – 150 Hz: 1 g
1 octave/min, 20 sweeps
● IEC 60068-2-27
(shocks during operation)
Test parameters:
15 g , 11 ms duration
6 shocks per axis
● IEC 60068-2-6
(vibrations during transportation)
Test parameters:
10 – 58 Hz: 0.075 mm
85 – 150 Hz: 1 g
1 octave/min, 20 sweeps