Data library
8.7 Formats
3WL/3VL circuit breakers with communication capability - PROFIBUS
256 System Manual, 03/2011, A5E01051353-02
Table 8- 41 PROFIBUS time format (DS100.4)
Byte Bit Meaning
0 — Higher-order digits of milliseconds
1 — Low-order digits of milliseconds
2 — Minute
3 0 - 4 Hour
3 7 1 = Summertime; 0 = Wintertime
4 0 - 4 Day of the month (1 ... 31)
4 5 - 7 Weekday (1 = Monday, ..., 7 = Sunday)
5 — Month
6 — Year (02 = 2002)
7 — Reserved
This time format is compliant with the PROFIBUS time format.