3WL air circuit breakers
3.5 External CubicleBUS modules
3WL/3VL circuit breakers with communication capability - PROFIBUS
60 System Manual, 03/2011, A5E01051353-02
The CubicleBUS is supplied with 24 V DC on X3. The table below shows the pin assignment
of X3 on the CubicleBUS module:
Table 3- 11 Pin assignment of the X3 on the CubicleBUS module
X3:1 Ground 24 V DC
X3:2 CubicleBUS communication cable -
X3:3 CubicleBUS communication cable +
X3:4 +24 V DC
3.5.1.4 Maximum configuration of the CubicleBUS
The CubicleBUS can comprise up to 13 nodes.
These include:
● Trip unit ETU
● Metering function PLUS
● Breaker Status Sensor (BSS)
● COM15
● BDA PLUS
● ZSI module
● Digital output module with switch position left (1st module)
● Digital output module with switch position right (2nd module)
● Digital configurable output module
● Digital input module with switch position left (1st module: "Parameterswitch")
● Digital input module with switch position right (2nd module: "PROFIBUS-Inputs")
● Analog output module with switch position left (1st module)
● Analog output module with switch position right (2nd module).
In practice, only one selection of these modules is usually necessary