EasyManua.ls Logo

Siemens SENTRON VL Series

Siemens SENTRON VL Series
286 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3WL air circuit breakers
3.5 External CubicleBUS modules
3WL/3VL circuit breakers with communication capability - PROFIBUS
System Manual, 03/2011, A5E01051353-02
77
Interfaces
The measured values can be picked up in the form of 0 - 10 V via the X4 connector on the
CubicleBUS module, and the 4 - 20 mA interface is available on the X5 connector. Both
output forms are always active simultaneously.
Figure 3-20 Analog output module
3.5.5.1 Selecting the measured values
The measured values output via the four analog channels are selected using a rotary coding
switch. The output forms I, V, P, f and cos ϕ are available. The selection box of the rotary
coding switch is divided vertically. If the switch is set to a value in the left half, the module is
automatically addressed as Module 1, so any second module must then be set to a value in
the right half. Only in this way is simultaneous operation with two analog output modules
possible.
Maximum assignment
Up to 2 analog output modules can be operated on one CubicleBUS.
Indicators
All rotary coil instruments with an inner flow resistance of more than 20 kΩ (as voltage
output) and between 50 Ω and 250 Ω (as current output) can be used as indicator. The LEDs
for the cannels show a yellow light when the current value exceeds 20% of the full-scale
deflection value (in the case of V, I, P), or cos ϕ is greater than 0.8, or the frequency is
greater than 45 Hz.

Table of Contents

Other manuals for Siemens SENTRON VL Series

Related product manuals