3WL air circuit breakers
3.7 External current consumption with CubicleBUS
3WL/3VL circuit breakers with communication capability - PROFIBUS
86 System Manual, 03/2011, A5E01051353-02
The table below provides the values for selecting the power supply with SITOP:
Table 3- 23 Power supply from the SITOP range for SENTRON WL with CubicleBUS
Max. continuous
current
Max. start-up current Type Order number
0 to 2 A Up to 7 A up to 300 ms SITOP Power 2 6EP1332-2BA10
2 to 5 A Up to 20 A up to 350
ms
SITOP Power 5 6EP1333-2BA01
5 to 10 A Up to 38 A up to 200
ms
SITOP Power 10 6EP1334-2BA01