EasyManua.ls Logo

Siemens SIMATIC 505 - Page 64

Siemens SIMATIC 505
216 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
505 SoftShop for Simatic 505 4 - 505 SoftShop Setup
57
connection to 505 TCP/IP #1 shown above. There should be four
successful replies to the PING command. If PING is not successful, there
is a problem with the network settings or the 505 TCP/IP board
configuration. If PING does not work, 505 SoftShop will not be able to
connect to the PLC.
After PING has successful replies, you can configure a TCP/IP
connection in 505 SoftShop and open an online window.
TCP/IP Communication Settings
To configure your interface board port for communication with a PLC:
1. From the Communications Setup dialog box, click the TCP/IP
button.
Result: The Settings for the TCP/IP Setup dialog box appear
(Figure 4.7).
Figure 4.7
2. Enter a unique IP Port protocol number, the response Timeout,
and Retries Number. Then Click the Accept button.
IP Port: Any number is acceptable as long as it does not
interfere with other protocol numbers. This number must
match the IP port configured in the 2572 Ethernet TCP/IP
module
Response T.O. (sec): Specifies the amount of time, in
seconds, that the software waits for a response from the
PLC before returning a time-out error. Any whole number
between 5 and 25 can be used.
Retries: Specifies the number of times the software will try
to re-establish communications with the PLC after a time-
out error. Any whole number between 0 and 10 can be used.
Use 0 for no retries.
IP Addresses
1. From the IP Addresses section of the TCP/IP Setup dialog box,
click the ADD button to enter a new IP address, or select an
existing IP address and click the Modify button to change the IP
information.
Result: The IP Addresses dialog box appears (Figure 4.8).

Table of Contents

Other manuals for Siemens SIMATIC 505

Related product manuals