Ambient conditions, tested according to IEC 61131-2
Ambient temperature for storage/transport, tested according to IEC 60068-2
• Min.
• Max.
• -40 °C
• 85 °C
Humidity without condensation during operation
• Min.
• Max.
• 5%
• 95%
Air pressure during operation
• Min.
• Max.
• 795 hPa (corresponds to an elevation of
2000 m)
• 1080 hPa (corresponds to an elevation of
-1000 m)
Vibration
• Operation
• Transport
• Tested according to IEC 60068-2-6
• Tested according to IEC 60068-2-6
Shock test Tested according to IEC 60068-2-27 and IEC
60068-2-31
Pollution degree according to ISA 71.04 G1; Operation in high ammonia and ozone envi‐
ronments is not included.
For operation in 3C2 environments, measures must
be taken to protect I/O system components from
salt spray (e.g. building structure, air conditioning).
Technical specications
10.2 Technical specications of components
CN 4100 Communication System
Equipment Manual, 10/2021, A5E50871363-AA 65