Technical data
16.1 Technical specifications of CPU 410-5H; (6ES7410-5HX08-0AB0)
CPU 410 Process Automation/CPU 410 SMART
258 System Manual, 05/2017, A5E31622160-AC
Article number
6ES7410-5HX08-0AB0
Autocrossing
Yes
System redundancy
Yes
Redundant subnetworks
Yes
Change of IP address at runtime, supported
No
Number of connection resources
120
Interface types
• Number of ports
2
• integrated switch
Yes
Media redundancy
• supported
Yes
• Switchover time on line break, typ.
< 200 ms
• Number of stations in the ring, max.
50
Functionality
• PROFINET IO Controller
Yes
• PROFINET IO Device
No
• PROFINET CBA
No
• Open IE communication
Yes
• Web server
No
PROFINET IO Controller
• Transmission rate, max.
100 Mbit/s
Services
– PG/OP communication
Yes
– S7 routing
Yes
– S7 communication
Yes
– Open IE communication
Yes
– Shared device
No; however, usable as part of S7
– Prioritized startup
No
– Number of connectable IO Devices,
max.
250
– Number of connectable IO Devices for
RT, max.
250
– of which in line, max.
250
– Activation/deactivation of IO Devices
Yes; Single mode only
– IO Devices changing during operation
(partner ports), supported
No
– Device replacement without swap me-
dium
Yes
– Send cycles
250 µs, 500 µs, 1 ms, 2 ms, 4 ms