Properties and technical specifications of CPU 410 SMART
17.2 Technical specifications of the CPU 410 SMART; (6ES7 410-5HN08-0AB0)
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
289
Article number
6ES7410-5HN08-0AB0
Global data communication
No
S7 basic communication
No
S7 communication
Yes
S7 communication, as client
Yes
S7 communication, as server
Yes
Equidistance
No
Isochronous mode
No
SYNC/FREEZE
No
Activation/deactivation of DP slaves
Yes; Single mode only
Direct data exchange (slave-to-slave
communication)
No
DPV1
Yes
Address area
Inputs, max.
1 536 byte; Up to 1 500 IOs (channels)
Outputs, max.
1 536 byte; Up to 1 500 IOs (channels)
User data per DP slave
User data per DP slave, max.
244 byte
Inputs, max.
244 byte
Outputs, max.
244 byte
Slots, max.
244
per slot, max.
128 byte
2. Interface
Interface type PROFINET
Physics
Ethernet RJ45
Isolated
Yes
automatic detection of transmission rate
Yes; Autosensing
Autonegotiation
Yes
Autocrossing
Yes
System redundancy
Yes
Redundant subnetworks
Yes
Change of IP address at runtime, supported
No
Number of connection resources
120
Interface types
Number of ports
2
integrated switch
Yes
Media redundancy
supported
Yes
Switchover time on line break, typ.
< 200 ms