Page #289 background image
Properties and technical specifications of CPU 410 SMART
17.2 Technical specifications of the CPU 410 SMART; (6ES7 410-5HN08-0AB0)
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
289
Article number
6ES7410-5HN08-0AB0
– Global data communication
No
– S7 basic communication
No
– S7 communication
Yes
– S7 communication, as client
Yes
– S7 communication, as server
Yes
– Equidistance
No
– Isochronous mode
No
– SYNC/FREEZE
No
– Activation/deactivation of DP slaves
Yes; Single mode only
– Direct data exchange (slave-to-slave
communication)
No
– DPV1
Yes
Address area
– Inputs, max.
1 536 byte; Up to 1 500 IOs (channels)
– Outputs, max.
1 536 byte; Up to 1 500 IOs (channels)
User data per DP slave
– User data per DP slave, max.
244 byte
– Inputs, max.
244 byte
– Outputs, max.
244 byte
– Slots, max.
244
– per slot, max.
128 byte
2. Interface
Interface type PROFINET
Physics
Ethernet RJ45
Isolated
Yes
automatic detection of transmission rate
Yes; Autosensing
Autonegotiation
Yes
Autocrossing
Yes
System redundancy
Yes
Redundant subnetworks
Yes
Change of IP address at runtime, supported
No
Number of connection resources
120
Interface types
• Number of ports
2
• integrated switch
Yes
Media redundancy
• supported
Yes
• Switchover time on line break, typ.
< 200 ms

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC CPU 410 and is the answer not in the manual?

Siemens SIMATIC CPU 410 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC CPU 410
CategoryControl Unit
LanguageEnglish

Related product manuals