Loading...
Properties and technical specifications of CPU 410 SMART
17.2 Technical specifications of the CPU 410 SMART; (6ES7 410-5HN08-0AB0)
CPU 410 Process Automation/CPU 410 SMART
290 System Manual, 05/2017, A5E31622160-AC
Article number
6ES7410-5HN08-0AB0
Number of stations in the ring, max.
50
Functionality
PROFINET IO Controller
Yes
PROFINET IO Device
No
PROFINET CBA
No
Open IE communication
Yes
Web server
No
PROFINET IO Controller
Transmission rate, max.
100 Mbit/s
Services
PG/OP communication
Yes
S7 routing
Yes
S7 communication
Yes
Open IE communication
Yes
Shared device
No; however, usable as part of S7
Prioritized startup
No
Number of connectable IO Devices,
max.
48
Number of connectable IO Devices for
RT, max.
48
of which in line, max.
48
Activation/deactivation of IO Devices
Yes; Single mode only
IO Devices changing during operation
(partner ports), supported
No
Device replacement without swap me-
dium
Yes
Send cycles
250 µs, 500 µs, 1 ms, 2 ms, 4 ms
Updating time
250 µs to 512 ms, minimum value depends on
the number of configured user data and the con-
figured single or redundant mode
Address area
Inputs, max.
1 536 byte; Up to 1 500 IOs (channels)
Outputs, max.
1 536 byte; Up to 1 500 IOs (channels)
User data consistency, max.
1 024 byte
Open IE communication
Number of connections, max.
118
Local port numbers used at the system end
0, 20, 21, 25, 102, 135, 161, 34962, 34963,
34964, 65532, 65533, 65534, 65535
Keep-alive function, supported
Yes