EasyManua.ls Logo

Siemens SIMATIC CPU 410

Siemens SIMATIC CPU 410
434 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Supplementary information
18.16 CPU 410 cycle and reaction times
CPU 410 Process Automation/CPU 410 SMART
System Manual, 05/2017, A5E31622160-AC
371
Calculation of the actual cycle time
Allowance for communication load (default value: 20%):
18.419 ms * 100 / (10020)
= 23.024 ms
.
There is no interrupt processing.
So the actual, cycle time is approx.
23 ms
.
Calculating the longest response time
Longest response time
23.024 ms * 2
= 46.048 ms
.
The delay of the inputs and outputs is negligible.
All the components are plugged into the central controller; DP cycle times do not
therefore have to be taken into account.
There is no interrupt processing.
So the longest, rounded up response time is
= 46.1 ms
.
Example II
You have installed an S7-400 with the following modules:
a CPU 4105H in redundant mode
4 digital input modules SM 421; DI 32×DC 24 V (each with 4 bytes in the PI)
3 digital output modules SM 422; DO 16xDC 24 V /2 (each with 2 bytes in the PI)
2 analog input modules SM 431; AI 8x13 bit (not in the PI)
2 analog output modules SM 432; AO 8x13 bit (not in the PI)
CPU parameters
The CPU parameters were assigned as follows:
Cycle load due to communication: 40%
User program
According to the instruction list, the user program runtime is 10.0 ms.

Table of Contents

Related product manuals